X2 base 7 - F2 I/O00A

7'' HMI with iX runtime and IOs

  • 800 × 480 pixel (16:9) TFT-LCD touch screen
  • Built-in digital and analog IOs
  • 200 MB application memory
  • 1 × Ethernet, 4 × serial, 1 × USB as standard
  • Operating temperature -10° to +50° C
  • CE, FCC

Important life cycle dates, read more -> Contact Print (PDF)

Facts

General description

Part number 630020105
Life cycle status Mature
Warranty 2 year

Certifications

General CE, FCC

Mechanical

Mechanical size 196 x 146 x 84mm
Mounting option Panel Mount
Number of touches 1million finger touch operations
Touch type Resistive
Cut-out size 186 x 136mm
Weight 0,9 kg
Housing material Plastic (PC+ABS), Gray
Buzzer Yes
LED Yes

Power

Input voltage 24 V DC (18 to 32 VDC)CE: The power supply must conformwith the requirements according to IEC 60950 and IEC 61558-2-4.UL and cUL: The power supplymust conformwith the requirements for class II power supplies.
Power consumption (max) 9.6W
Input fuse Internal DC fuse

System

CPU ARM9 400 MHz
RAM 128 MB
FLASH 256 MB, 200 MB free

Display

Size diagonal 7" diagonal
Resolution 800x480 pixels
Backlight LED Backlight
Backlight life time 20000 hours
Backlight brightness 400 cd/m2
Backlight dimming Industrial Dimming
Display type TFT-LCD with LED backlight

Digtal IO

Digital input 8 inputs, 24 VDC at 5.6mA (0.13W per input)
Cofiguration 2 isolated, independent groups with 4 inputs per group. Each group shares one common contact. Supports sink/source mode for each group.
Type IEC 61132-2 Type I
Isolation 550 VAC, 1min
Digital output 6 outputs, 30 VDC, 3A max
Configuration 3 isolated, independent groups with 2 outputs per group. Each group shares one common contact.
Type Relays (contact configuration: SPST-NO)
Isolation 550 VAC, 1min

Analog IO

Analog input channels 4
Input type 0-10V or 4-20mA
Input impedance According to EN 61131-2
Galvanic isolation No
Resolution 14 Bit (0-10V: 0…16383 / 4-20mA: 3277…16383)
Conversion time 100ms per channel
Accuracy 0.3%
Analog output channels 2
Output type 0-10V or 4-20mA
Output impedance According to EN 61131-2
Galvanic isolation No
Resolution 14 Bit (0-10V: 0…16383/4-20mA: 3277…16383)
Conversion time 100ms
Accuracy 0.3%

Serial communication

Number of serial ports 2 Port 9pin DSUB
Serial port 1 RS 232 (RTS/CTS)
Serial port 2 RS422/485
Serial port 3 RS 232
Serial port 4 RS 485

Ethernet communication

Number of Ethernet ports 1
Ethernet port 1 1x10/100 Base-T (shielded RJ45)

Expansion interface

Expansion port No
SD card No
USB 1xUSB 2.0 400mA

Environmental

Operating temperature -10°C to +50°C
Storage temperature -20° to +60°C
Shock 15g, half-sine, 11ms according to IEC60068-2-27
Vibration 1g, according to IEC 60068-2-6, Test Fc
Sealing front IP65
Sealing back IP20
Humidity 5% – 85% non-condensed

Resources

Drawings

File name Date
CAB108 Cable Drawing for X2 base, X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C iX operator panel 2022-09-20 15:55:15
CAB110 Cable Drawing for X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C operator panel 2022-09-20 15:57:35
CAB105 Cable Drawing for X2 base, X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C operator panel 2022-10-10 08:36:51
CAB106 Cable Drawing for X2 base, X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C operator panel 2022-09-20 15:58:03
CAB107, 25-pol to 9-pol adapter, Cable Drawing for X2 base, X2 pro, X2 marine, X2 control, iX Panel TxA/B/C operator panel 2022-09-20 15:57:58
CAB109 Cable Drawing for X2 base, X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C iX operator panel 2022-09-20 15:58:14
Cable CAB113: Cable for ModBus RS485 between X2 panel and BFI 2022-10-05 14:15:53
CAB153 Cable Drawing for X2 base, X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C operator panel 2022-10-10 08:38:06
CAB150 Cable Drawing for X2 base, X2 pro, X2 marine, X2 control, iX Panel TxA/B/C operator panel 2022-10-10 08:37:51
CAB104 Cable Drawing forX2 base, X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C operator panel 2022-10-10 08:36:52
CAB103 Cable Drawing for X2 base, X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C 2022-10-10 08:36:50
CAB101 Cable Drawing for X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C operator panel 2022-10-10 08:36:49
CAB100 Cable Drawing for X2 pro, X2 marine, X2 control, X2 motion, iX Panel TxA/B/C operator panel 2022-09-20 15:57:40

System program

File name Date
TxA, X2 base image 1.12 b1335 (Current version) 2022-10-10 08:49:02

Information document

File name Date
Input regarding unsuported Drivers for X2 base (v1)/BoX2 base (v1) 2024-02-01 10:42:28
​Guidelines for TxA and TxB migration to X2. 2022-10-10 08:38:10

Manuals

File name Date
iX Developer Reference Manual, MAEN355 rev. B (current version) 2023-09-19 14:12:01

Drivers

File name Date
iX and Allen-Bradley Ethernet CLX 2022-09-21 12:36:46

Configuration files

File name Date
EDS file for CiX-CAN and X2 2022-09-28 13:38:21

Brochures

File name Date
X2 series (German) 2022-09-21 08:11:38
X2 brochure (Spanish)​ 2022-09-21 08:12:32
X2 brochure 2019 (French) 2024-01-15 10:52:15
X2 brochure (English), BREN631 2022-09-21 08:11:56
Limited availability

X2 base 7 - F2 I/O00A

7'' HMI with iX runtime and IOs


EOL - End Of Life:
-

LTB - Last Time Buy:
2023-12-31

LTD - Last Time Delivery:
-

LTR - Last Time Repair:
-

Replacement Parts: