M9372
Programmable I/O with CODESYS
- 2 x Ethernet 10/100Mbps
- 16 MB program memory
- 16 MB data/32 KB Non-Volatile memory
- Up to 63 expansion slices
- M7001 power module
- 18pt removable terminal block (RTB18C)
Facts
General description
Article number | 100-8201 |
Warranty | 2 year |
Article status | Active |
Shock operating | IEC 60068-2-27 (15G) |
Vibration resistence | Sine vibration (based on IEC 60068-2-6), DNVGL-CG-0339 (Vibration Class B, 4G) |
Industrial emissions | EN 61000-6-4/2019 |
Industrial immunity | EN 61000-6-2 : 2019 |
Installation position | Horisontal, Vertical |
System power | UL System Power: Supply voltage : 24 VDC nominal, Class 2 System Power, Supply voltage : Class 2, 24 VDC nominal, Supply voltage range : 15~28.8 VDC, Protection : Output current limit / Reverse polarity protection |
Power dissipation | 110 mA typical @ 24 VDC (PIO+Power Module), (Network Adapter : 80 mA typical @ 24 VDC), (M7001 Module : 30 mA typical @ 24 VDC) |
Current for IO module | 2.0A @ 5 VDC (If except for NA, current for I/O module is about 1.7A) |
Isolation | System power to internal logic : Non-isolation, System power I/O driver : Isolation |
Field power | Supply voltage : 24 VDC typical (Max.28.8 VDC), * Field Power Range is different depending on IO Module series. Refer to IO Module`s Specification. |
Max current field power contact | DC 10A Max |
Weight | 179g |
Module size | 54mm x 110mm x 75mm |
Certifications
General | CE, FCC, UL, cUL |
Hazardous | ULC1D2, ATEX (Zone2) |
Marine | DNV GL |
Safety | UL508, CAN/CSA C22.2 No.142-M1987 |
Communication
Redundancy | No |
Station type | Master & Slave Node (Modbus TCP, Modbus RTU) |
Max expansion ports | 63 slices |
IO data size | 128 bytes (input + output) |
Baud rate | 2400 ~ 115 200bps (RTU), 10/100Mbps, Auto-negotiation, Full Duplex (TCP) |
Bus connection | 9pin D-sub (RTU), 2 x RJ45 (TCP) |
Other serial port | RS232 for MODBUS RTU (Touch Panel or IOGuide) |
Serial configuration | Node: 1 (Fixed), Baud Rate: 115200 (Fixed), Data bit: 8 (Fixed), Parity bit: No parity (Fixed), Stop bit: 1 (Fixed) |
Indicator | 4 LEDs: 1 Green/Red, Module Status (MOD), 1 Green/Red, Network Status (NET), 1 Green/Red, PLC Run/Stop Status (RUN), 1 Green/Red, Expansion I/O Module Status (IOS) |
Module location | Starter module left side |
Field power detection | ~14VDC |
Environmental
Mounting | 35mm DIN rail |
Operating temperature | -25 ~ 60℃ |
Storage temperature | -40 ~ 85℃ |
UL temperature | -25 ~ 60℃ |
Relative humidity | 5 ~ 90% non-condensing |
Power module specifications
Contact voltage | DC 10A Max |
Field power voltage | 24VDC |
Indicator | M7001: 4 LEDs, 1 Green, M-Bus Status (RUN), 1 Green, Primary Status(PRI), 1 Green, Active Status (ACT), 1 Green, Field Power Enable (Field Power) |
Input voltage range | 15 VDC to 28.8 VDC |
Power input voltage | 24VDC |
Resources
Firmware
File name | Date | |
---|---|---|
M series, M9372 PIO - Firmware update | 2023-12-18 14:21:26 |
Configuration files
File name | Date | |
---|---|---|
M-Series Programmable IO - Device Description (XML) | 2024-07-07 07:31:05 |
Knowledge
File name | Date | |
---|---|---|
M937x PIO and Non-volatile memory adjustments! (Retain) | 2023-09-21 13:26:31 | |
Online change with Update boot application will delay scantime | 2023-08-10 20:58:10 | |
CODESYS Trace feature for PIO modules | 2024-08-09 08:51:11 | |
Ethernet port specification of G- / M-series PIO and Network adapters | 2024-05-03 07:55:52 | |
Always add a power module (M7001/7002) after the network adapter | 2023-08-09 15:20:30 | |
BCS Tools - SFC errors at compile | 2024-02-07 08:21:44 | |
Programmable IO - Release Notes / Revision history | 2024-04-19 10:14:26 | |
Common noise filter NBH-06-432-D to FnIO S- and M-series (for DNV certificate) | 2022-09-06 11:36:38 | |
FnIO M-, G- and S-series Serial number and Production date | 2023-07-20 11:30:16 | |
Shock resistance of G- and M-series (IEC 60068-2-27) | 2022-09-06 14:16:00 | |
How to download Free software packages from SmartStore | 2023-08-08 15:52:30 |
Program examples/Start-up
Software
File name | Date | |
---|---|---|
PIO Firmware Update Tool (for G- and M-series) | 2023-08-03 17:19:35 | |
CODESYS V3.5 SP11 Patch 3, required for G- and M-series PIOs FW rev 2.xxx | 2023-03-15 14:55:35 | |
IO Guide Pro 2.0.0.0 beta (20231128), for Beijer G- and M-series | 2024-09-24 08:11:21 |
Manuals
File name | Date | |
---|---|---|
Manual: Solution Modbus RTU communication Nexto PLC/X2control/PIO with BFI-P2 BFI-H3 BFI-E3 | 2024-08-01 14:51:06 | |
Manual: Solution Modbus TCP communication Nexto/X2control/PIO PLC with BFI-E3 | 2024-08-07 12:01:27 | |
Manual: Solution Modbus TCP communication Nexto/X2control/PIO PLC with BFI-P2 BFI-H3 | 2024-08-07 15:16:24 | |
M937x M-Series Programmable IO (M9371 / M9372 / M9373) | 2022-09-06 11:38:43 | |
M-Series Common User Guide & Hotswap functionality | 2022-09-06 14:15:24 |
Drawings
File name | Date | |
---|---|---|
Remote IO serial Modbus RS485 wiring (RTU) | 2023-04-04 16:18:48 | |
M-series Drawing, 2D CAD files (Electrical) | 2023-02-23 15:28:43 | |
M-series Drawing, 3D / 2D CAD files (Mechanical) | 2023-02-23 15:28:30 |
Product information
File name | Date | |
---|---|---|
Conversion guide for alternative products between S-series remote IO to G- or M-series | 2022-09-06 11:38:29 |
Certificates
File name | Date | |
---|---|---|
UL & cUL Certificate of compliance - Beijer M-series | 2022-11-11 08:37:00 | |
UL-HAZLOC Certificate of compliance - Beijer M-series | 2022-11-11 08:37:24 | |
DNV GL - Type Approval Certificate (Revision 1) - Beijer M-series | 2022-11-11 08:37:59 | |
DNV approval Fnio M-series DNV GL - Type Approval Certificate | 2024-09-13 09:20:04 | |
Beijer M-series certificate overview | 2022-11-17 07:00:20 | |
ATEX Zone 2 Certificate - Beijer FnIO M-series | 2022-11-15 08:20:20 | |
CE DoC - Beijer M-series including EMC, LVD, RoHS-II & Reach | 2024-02-21 21:13:26 | |
FCC DoC - Beijer M-series | 2022-11-11 08:35:14 |
Information document
File name | Date | |
---|---|---|
Beijer M-series Caution and Warning (ATEX & RoHS) Rev.3.02 | 2022-11-11 08:55:42 |
Smart Engineering Resources
Limited availability
M9372
Programmable I/O with CODESYS
EOL - End Of Life:
-
LTB - Last Time Buy:
-
LTD - Last Time Delivery:
-
LTR - Last Time Repair:
-
Replacement Parts: