BCS-NX6020
RTD input module
- 8 RTD inputs
- Software configurable ranges
- Under and over range diagnostics
- Display for module diagnostics and input state indication
- Removable terminal blocks with support for field wiring fixation
- Hot-Swap
- One touch diagnostics for easy maintenance
Facts
General description
Article number | 66.014.324-0 |
Warranty | 2 year |
Mechanical
Certificates | CE, ROHS, UL, DNV |
Module dimensions (W x H x D) | 18.00 x 114.63 x 117.46 mm |
Net weight | 200 g |
Power
Current consumption from backplane rack | 300 mA |
System
Hot Swap | Yes |
One Touch Diag (OTD) | Yes |
Status and diagnostics indication | Yes |
Converter resolution | 24 bits monotonicity guaranteed, no missing codes |
Data format | 16 bits in two’s complement, justified to the left |
Measurement unit | Configurable: °C or °F |
Precision | PT100/PT1000 ± 0.5 °C @ 25 °C |
Ranges | Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, 0 - 400 Ω and 0 - 4000 Ω |
Digital IO
Update time | 12.5 ms per channel (without suppression filter) |
Resources
Manuals
- BCS-NX6020 - Installation Guide
- BCS-NX6020 - User's manual
- BCS Nexto modular/Nexto Xpress - PID advanced library
- BCS Tools - User Manual
- BCS Tools - Programming Manual
- BCS Tools - Datasheet
- BCS NX940x - User's manual (Connectors of Nexto Series)
- BCS NX92xx - User's manual (RJ45-RJ45 Cables)
- BCS Nexto Series - User Manual
Program examples/Start-up
- Nexto - Library supporting NI1000LG sensor type
- Program example BCS Tools and iX: Nexto communication with BFI by EtherCAT
- Kom i gang med Nexto XPress - Høyhastighets datalogging (Norwegian)
- BCS Tools/Nexto - Modbus TCP and Crevis I/O, init ST-3702
- Program example BCS Tools and iX: Nexto Xpress communication with BFI by Modbus RTU.
- Kom i gang med Nexto XPress - SQL kommunikasjon (Norwegian)
- Kom i gang med Nexto XPress - MQTT kommunikasjon (Norwegian)
- Kom i gang med Nexto XPress - HTML5 websider (Norwegian)
- Kom i gang med Nexto XPress - Grunnleggende (Norwegian)
- Get Started with Nexto Xpress - MQTT communication
- Get Started with Nexto Xpress - The Basics
- Get Started with Nexto Xpress - High speed datalogging
- BCS Tools, MODBUS Symbol Server/Client
- Get started with Nexto Xpress - IEC60870-5-104
- Get Started with Nexto Xpress - Database communication
Software
Drawings
Firmware
Data sheets
Knowledge
- BCS NX6010 - Is it possible to connect mV signal from load cell transmitters
- BCS-NX6000 - Single end or differential inputs?
- BCS-Nexto/Nexto Xpress - Number of supported ARTI connections
- Clarification about the force function in CODESYS
- BCS Tools - The address %QBxxxxx not defined in any device
- BCS Tools - OPC connection to the CPU or the simulator in BCS Tools.
- BCS Nexto - ARTI/OPC communication
- Example of a Modbus/TCP client via PLC code using the Oscat library
- BCS Nexto Xpress/Modular - MQTT version
- LTB Life Cycle Notification BCS-NX940x spareparts
- Nexto I/O update with EtherCat master
- Nexto - Persistent variables loose their value if the name of the application changes
- Nexto - Check operating status of I/O modules
- BCS Tools - Edit CSV files with Excel 2013 or newer might destroy and make the csv files unusable for BCS Tools
Catalogues
Certificates
- BCS Nexto modular - DNV approval
- BCS Nexto/Nexto Xpress - UL/cUL certificate
- BCS Nexto Modular - CE EMC/LVD Declaration
Information document
Configuration files
Limited availability
BCS-NX6020
RTD input module
EOL - End Of Life:
-
LTB - Last Time Buy:
-
LTD - Last Time Delivery:
-
LTR - Last Time Repair:
-
Replacement Parts: